Project note: The base thickness, concrete class, reinforcement, excavation allowance, pipe diameter and quantities mentioned in this guide are preliminary planning examples; they do not constitute a structural design that can be applied to every site. A qualified engineer must prepare the design after evaluating the geotechnical investigation, groundwater, loads and local rules. Even in a full pool, if the external water load exceeds the internal water load, hydrostatic effects and liner lifting can occur; draining, drainage and electrical work require expert supervision.
In pool construction, the most critical network of lines, invisible once the site work is finished and buried under the backfill, is the pool's suction and return pipework. Using non-pressure waste water pipe or thin-walled pipe to cut costs significantly increases the risk of damage to the pipe and joints under the vacuum and pressure surges (water hammer) created by the pump. Repairing an underground pipe leak generally means ruining the landscaping and carrying out extensive excavation. The Sermed Pools standard for underground runs calls for at least PN10 class rigid PVC pipe on suction lines and PN16 class on return lines, pressure-rated fittings, and a two-stage solvent jointing protocol (cleaner plus cement).
Pipe that stays underground cannot be left to chance. A correctly selected and correctly jointed PVC pipe run is the most important invisible backbone for trouble-free operation of the pool's water lines over many years.
01. Pipe Collapse Underground: Water Hammer and the Disaster of Thin Wall Thickness
Serious pipe failures encountered in pool hydraulic pipework:
- Pipe Crushing Under Vacuum: Negative pressure forms on the suction line while the circulation pump is running. Thin-walled, non-pressure waste water pipe can buckle inward and fracture under this condition.
- Water Hammer: When the pump stops suddenly or valves are closed quickly, shock pressure waves form inside the pipe that can reach several times the working pressure; poorly cemented joints can be forced open by this surge. The actual surge value depends on the line length, flow velocity and valve closing time.
- Soil Load and Crushing by Stone: During backfilling, the point loading of crushed stone can crush or puncture thin-walled pipe; thick-walled PN10/PN16 pipe is markedly more resistant to external mechanical effects.
02. Sermed Pools Pipework Standard: PN10 / PN16 Pressure Class and Solvent Jointing
The Sermed Pools mechanical installation standard is applied according to these rules:
- PN10 (10 Bar) and PN16 (16 Bar) Rigid PVC: At least PN10 is used on suction lines (for example Ø50 mm or Ø63 mm, depending on the project), while PN16 class thick-walled pressure PVC pipe and couplings are used on return lines. The diameter is selected on the basis of flow rate and flow velocity calculations.
- Chemical Cold Welding: The pipe ends are first wiped with a manufacturer-approved cleaner solvent to remove surface dirt and manufacturing oil; PVC solvent cement is then applied and the pipe is pushed fully home into the socket in accordance with the product instructions, producing a continuous solvent-welded joint. Application and curing times follow the product label.
- Sand Bedding: Underground pipes are never laid directly on sharp stone; sieved sand or fine gravel is spread beneath and above the pipe trench to form a mechanical protection bed. The bedding thickness is set by the project; a common reference value is 10 cm.
- Pressure Testing: Before the pipes are covered, the lines are filled with water and test pressure is applied with a gauge; backfilling is not permitted until it has been confirmed that there is no pressure drop over the test pressure and duration set by the project and material class. A common field practice is 3 bar held for 24 hours.
03. Pool Pipe Classes: Strength and Application Table
| Pipe Type and Class | Working Pressure Rating | Resistance to Vacuum and Soil Load | Suitability for Pool Pipework |
|---|---|---|---|
| Standard Waste Water Pipe | Not suitable for pressure use (very low) | Very weak (crushes and cracks) | MUST NOT BE USED ON PRESSURE LINES |
| Yellow Drainage Pipe | Non-pressure (perforated) | For water drainage only | Cannot be used on pressure lines |
| PN10 Rigid PVC (Ø50/63) | 10 bar nominal pressure | High (resistant to vacuum) | THE STANDARD FOR SUCTION LINES |
| PN16 Pressure PVC | 16 bar nominal pressure | Maximum (resistant to pressure surges) | THE STANDARD FOR RETURN AND HEATING LINES |
Conclusion: Repairing underground pipe is difficult and costly. PN10/PN16 pressure PVC pipe, correct solvent jointing and a pressure test before covering are decisive for the safety of the water lines.
Frequently asked questions
Why are joint quality and the choice of pressure-rated PVC pipe so critical for pool pipes that remain below ground?
Pipes that remain underground are exposed to the dynamic pressure of the water, the vacuum of the pump and the weight of the backfill; non-pressure pipe can be crushed and split under these conditions. PN10/PN16 pipes resist pressure thanks to their greater wall thickness, and solvent cement forms a continuous joint intended to reduce the risk of leakage.
Can flexible spiral PVC hose be used for the pipework?
On short bends and at vibration damping points, flexible PVC pipe with a suitable pressure class and spiral reinforcement can be used. On long straight runs, rigid PVC pipe is preferred because it does not sag and has better dimensional stability.
How is a pressure test carried out?
All outlets of the pipe runs are closed with blanking plugs; the project test pressure (commonly 3 bar in the field) is applied to the system with a test pump and a gauge is connected. The absence of any pressure drop over the specified period (commonly 24 hours) indicates watertightness.
How many centimetres deep should pipes be buried to prevent freezing?
Burial depth is determined by the frost depth at the project location, local practice rules and the type of line; no single universal value can be given. An example planning assumption representing mild coastal conditions is 40-50 cm, while for cold, high-altitude conditions it is 80 cm or more. These values are examples only; the exact depth must be verified against local frost depth data. Lines should also be laid on a slope so that they can be drained, and the water must be discharged when the season is closed.